MTS3 semacam Pemutus Pengukuran AIOT dan dapat digunakan untuk pengawasan keamanan listrik cerdas dan solusi manajemen daya. Produk ini termasuk Meter, Perlindungan listrik penuh (korsleting + kelebihan beban + tegangan lebih / kurang + kebocoran bumi + AFDD + lonjakan & petir + kehilangan fase + unblance + suhu.), Timer, analisis kesalahan, remote control, batas daya / arus, uji otomatis arus bocor,
Spesification :
Technical specification of Communicaiton Module
Item Code: MTS3-C
Standards: EN301489,EN300328,EN62479,EN60950
Approvals: CE,CCC
Types TCP/IP, RS485,Wifi, GPRS-2G, NB-ioT, Zigbee, Lora
Rated input Voltage 12
Numbers of Modules( 1 module=18mm) 1 (18mm)
Max. working capacity ( Max.numbers of breaker powering) 3 iRCBO+ 8 iMCB
Conductor cross-sections 38
Pollution Degree 2
Ambient temperature: -15 – +40
Storage temperature: -25—+70
Humidity < 95%
Altitude: <=2000
Terminal Connection Cable/Pin-type busbar
Mounting Din rail En60715(35mm) by means of fast clip device
Connection From top to bottom
Technical specification of Power Module
Power supplier Module may offer stable DC power for Smart Breaker MTS3 and has Class II Surge Protection. It is also the necessory part for Smart Breaker MTS3 system.
Item Code: MTS3-P25N MTS3-P25D
Standards: EN55022, EN55024,EN61000,EN60950,GB4943
Approvals: CE,CCC
Functions Power supplier, Surge Protection
Rated voltage Un: 220
Rated input voltage Range: 100-265
Frequency (HZ): 50/60
Rated input Current 350
Rated output Voltage 12
Rated output Current 2.5
Type / test class of Surge Protection: 2 / II
Numbers of Modules( 1 module=18mm) 36(2 P)
Max.Cont. operating voltage Uc: 175, 275
Max.discharge current Imax (8/20) per pole Imax: 15
Nominal discharge current In (8/20) per pole In: 10
Max. working capacity ( Max.numbers of breaker powering) 1 iRCBO+8 iMCB
Conductor cross-sections 38
Pollution Degree 2
Ambient temperature: -15 – +40
Storage temperature: -25—+70
Humidity < 95%
Altitude: <=2000
Terminal Connection Cable/Pin-type busbar
Mounting Din rail En60715(35mm) by means of fast clip device
Connection From top to bottom
Technical specification of Smart Breaker Modules
Smart Breakers are the core part of MTS3 smart system,it combine protection, metering, monitor, timer,automation, event record and notice.
Item Code: MTS3-M1 MTS3-M2 MTS3-M3 MTS3-M4
Standards: IEC60898, GB10963.1
Approvals: CE,CCC
Poles 1P 2P 3P 4P
Rated voltage Ue 230/400-240/415
Operational voltage Min.90 Max:250/440
Frequency (HZ): 50/60
Rated Current 10,16,20,25,32,40,50,63,80
Rated insulation voltage Ui 500
Rated impulse withstand voltage (1.2/50) Uimp 2500
Rated Breaking capacity acc.to IEC60899 Icn 6000
Breaking time under Icn <=0.04S
Triping Characteristic B (3-5In)
C (5-10In)
D (10-14In)
Other Functions
Over/under voltage protection , warning and Alarm
Max.Power and Current Setting
Auto test of earth leakage current
High Temperature protection, warning and Alarm
Arcing Fault Protection, warning and Alarm
Monitor of Current, power, voltage in real-time
Remote control
Timer
Meter
Event record and notice
Breaking time when voltage is over 263Vac 10S
Over/undder voltage warning when voltage is higher than 250Vac or lower than 190Vac
Breaking time when the current reach the max.current or power setup 5s
Electric Life 10000
Mechanical life 20000
Conductor cross-sections 38
Pollution Degree 2
Numbers of Modules( 1 module=18mm): 1.5 (27mm) 2.5 (45mm) 4 (72mm) 5(90mm)
Ambient temperature: -15 – +40
Storage temperature: -25—+70
Humidity < 95%
Altitude: <=2000
Terminal Connection Cable/Pin-type busbar
Mounting Din rail En60715(35mm) by means of fast clip device
Connection From top to bottom
Technical specification of Smart RCBO Modules
Smart RCBO may be used as main switch and line protection in Smart Breaker MTS3 system. It is also the necessory part for Smart Breaker MTS3 system as main switch.
Item Code: MTS3-R2 MTS3-R4
Standards: IEC61009, GB16917.1
Approvals: CE,CCC
Poles 2P 4P
Rated voltage Ue 230 400
Frequency (HZ): 50/60
Rated Current 16,20,25,32,40,50,63,80
Type (wave form of the earth leakage sensed) AC
Rated residual current (I n) 30
Rated insulation voltage Ui 500
Rated Breaking capacity acc.to IEC61009 ultimate Icn 6000
Breaking time under I n <=0.1 S
Breaking time under Icn <=0.04S
Triping Characteristic C (5-10In)
Other Functions
Over/under voltage protection , warning and Alarm
Max.Power and Current Setting
Auto test of earth leakage current
High Temperature protection, warning and Alarm
Monitor of Current, Power and Voltage in real-time
Arcing Fault Protection, warning and Alarm
Remote control
Timer
Meter
Event record and notice
Breaking time when voltage is over 265Vac 10S
Over/undder voltage warning when voltage is higher than 250Vac or lower than 190Vac
Breaking time when the current reach the max.current or power setup 5s
The time for Switching on automatically after auto-test of earth leakage current 5s
Electric Life
Mechanical life
Conductor cross-sections 38
Pollution Degree 2
Numbers of Modules( 1 module=18mm) 3 (54mm) 5 (90mm)
Ambient temperature: -15 – +40
Storage temperature: -25—+70
Humidity < 95%
Altitude: <=2000
Terminal Connection Cable/Pin-type busbar
Mounting Din rail En60715(35mm) by means of fast clip device
Connection
From top to bottom
There are no reviews yet.